Help

Vertiv - Vertiv Liebert GXT5

UPS (rack-mountable / external) - AC 120 V - 1800 Watt - 2000 VA - 1-phase - Ethernet, USB, serial - output connectors: 7 - 2U - TAA Compliant

Vertiv
GXT5-2000LVRT2UXLTAAN
N/A
N/A
New

Price: $2,508.00

Total Available: 21

Product Description

Additional Details

What's Included

Specifications

Main Specifications
Product Description Vertiv Liebert GXT5 - UPS - 1800 Watt - 2000 VA - TAA Compliant
Device Type UPS - rack-mountable / external
Rack Size 2U
Weight 47.62 lbs
Input Wiring 1-phase
Input Voltage AC 120 V
Output Voltage AC 110/115/120 V ± 3%
Power Capacity 1800 Watt / 2000 VA
Input Connectors 1 x power NEMA L5-20P
Output connectors 6 x power NEMA 5-20R ¦ 1 x power NEMA L5-20R
Battery Lead acid
Run Time (Up To) 4 min at full load
Networking Ethernet, USB, serial
Remote Management Protocol SNMP
Included Accessories Tower stand
TAA Compliant TAA Compliant
Dimensions (WxDxH) 16.9 in x 18.5 in x 3.3 in
Environmental Standards ENERGY STAR
Manufacturer Warranty 3-year warranty
General
Device Type UPS - rack-mountable / external
Height (Rack Units) 2U
Expansion / Connectivity
Interfaces 1 x USB - 4 pin USB Type B ¦ 1 x RS-485 ¦ 1 x RS-232 ¦ Dry contact ¦ 1 x management (Ethernet) - RJ-45 ¦ 1 x sensor ¦ 1 x USB - 4 pin USB Type A
Expansion Slots 1 (total) / 0 (free) x Liebert IntelliSlot
Manufacturer Warranty
Service & Support Limited warranty - advanced replacement - 3 years
Miscellaneous
Included Accessories Tower stand
Cables Included Power cable 10 ft ¦ USB cable - external
Rack Mounting Kit Included
Equipment Protection Value 500000 US Dollars
Features Hot-swappable battery, replaceable battery, LCD display, overcurrent protection, Auto-Sensing Technology, 4 programmable sockets, double conversion, environmental sensor ready
Compliant Standards WEEE, FCC Part 15 A, REACH, CSA C22.2 No. 107.3, RoHS2, ISTA 1A, AS/NZS CISPR22 Class A, ANSI C62.41 Category B, UL 1778 4th edition
TAA Compliant Yes
Networking
Remote Management Interface Ethernet, USB, serial
Remote Management Protocol SNMP
Software / System Requirements
Software Included Trellis Power Insight
Environmental Parameters
Min Operating Temperature 32 °F
Max Operating Temperature 104 °F
Humidity Range Operating 0 - 95% RH (non-condensing)
Sound Emission 48 dBA
Battery
Technology Lead acid
Run Time (Up To) 4 min at full load ¦ 12.3 min at half load ¦ 22 min at full load with extended capacity battery ¦ 53.6 min at half load with extended capacity battery
Features Spill-proof, valve-regulated
Power Device
UPS Technology On-line
Input Voltage AC 120 V
Input Voltage Range AC 60 - 150 V
Input Wiring 1-phase
Frequency Required 40 - 70 Hz
Input Connectors 1 x power NEMA L5-20P
Power Output Connectors Details 6 x power NEMA 5-20R ¦ 1 x power NEMA L5-20R
Output Voltage AC 110/115/120 V ± 3%
Power Capacity 1800 Watt / 2000 VA
Output Waveform Sinewave
Surge Suppression Yes
Efficiency 98% Eco mode, 95% online mode
Power Factor (PF) 0.9
Dimensions & Weight
Width 16.9 in
Depth 18.5 in
Height 3.3 in
Weight 47.62 lbs
Environmental Standards
ENERGY STAR Yes

Related Products

Below are the optional products related to the selected product.