Help

Panduit - Panduit SmartZone

UPS (rack-mountable / external) - AC 100-125 V - 3000 Watt - 3000 VA - 1-phase - Ethernet, RS-232, USB - output connectors: 5 - PFC - 2U - North America - black

Panduit
U03N11V
0613056825260
N/A
New

Price: $1,937.00

Total Available: 3

Product Description

Additional Details

What's Included

Specifications

Main Specifications
Product Description Panduit SmartZone - UPS - 3000 Watt - 3000 VA
Device Type UPS - Power Factor Correction (PFC) - rack-mountable / external
Rack Size 2U
Weight 56.66 lbs
Localization North America
Input Wiring 1-phase
Input Voltage AC 100-125 V
Output Voltage AC 100/110/115/125 V
Power Capacity 3000 Watt / 3000 VA
Input Connectors 1 x power NEMA L5-30P
Output connectors 4 x power NEMA 5-20R ¦ Power NEMA L5-30R
Battery Lead acid
Batteries Qty 6
Run Time (Up To) 4.6 min at full load
Networking Ethernet, RS-232, USB
Remote Management Protocol SNMP 3
Color Black
Dimensions (WxDxH) 17.3 in x 23.6 in x 3.4 in
Environmental Standards ENERGY STAR
Manufacturer Warranty 3-year warranty
General
Device Type UPS - Power Factor Correction (PFC) - rack-mountable / external
Height (Rack Units) 2U
Color Black
Localization North America
Expansion / Connectivity
Interfaces 1 x management (USB) ¦ 1 x management (RS-232) ¦ 1 x EPO (emergency power off) ¦ 1 x management (Ethernet) - RJ-45 ¦ 1 x sensor - RS-485
Expansion Slots 1 (total) / 1 (free) x Intelligent Slot
Manufacturer Warranty
Service & Support Limited warranty - 3 years ¦ Limited warranty - batteries - 2 years
Miscellaneous
Cables Included Power cable 10 ft
Rack Mounting Kit Included
Features Audible alarm, emergency power off, LCD display, overheat protection, internal bypass, Automatic Voltage Regulation (AVR), overcharge protection, overload protection, short-circuit protection, hot-swappable batteries, low voltage protection, overdischarge protection, double conversion, fan failure protection, 2 programmable sockets
Compliant Standards cUL, REACH, FCC Part 15 B Class A, IP20, ANSI C63.4-2014, ISTA 2A, UL 1778 5th edition, ANSI C62.41 Category A, RoHS 2.0, CSA C22.2 No.107.3-14
Networking
Remote Management Interface Ethernet, RS-232, USB
Remote Management Protocol SNMP 3
Software / System Requirements
Software Included SmartZone Cloud, SmartZone mPower
Environmental Parameters
Min Operating Temperature 32 °F
Max Operating Temperature 104 °F
Humidity Range Operating 0 - 95% RH (non-condensing)
Sound Emission 55 dB
Battery
Quantity 6
Technology Lead acid
Voltage Provided DC 72 V
Run Time (Up To) 4.6 min at full load ¦ 14.1 min at half load
Recharge Time 6 hours
Transfer Time 4 ms
Features Maintenance free, valve-regulated
Power Device
UPS Technology On-line
Input Voltage AC 100-125 V
Input Voltage Range AC 55 - 150 V
Frequency Provided 50/60 Hz
Input Wiring 1-phase
Frequency Required 40 - 70 Hz
Input Connectors 1 x power NEMA L5-30P
Power Output Connectors Details 4 x power NEMA 5-20R ¦ Power NEMA L5-30R
Output Voltage AC 100/110/115/125 V 50/60 Hz
Power Capacity 3000 Watt / 3000 VA
Dataline Surge Protection Network - RJ-45
Output Waveform Sinewave
Efficiency 92% online mode, 96.5% Eco mode
Power Factor (PF) 1.0
Dimensions & Weight
Width 17.3 in
Depth 23.6 in
Height 3.4 in
Weight 56.66 lbs
Dimensions & Weight (Shipping)
Shipping Width 21.9 in
Shipping Depth 28.7 in
Shipping Height 8 in
Shipping Weight 69.89 lbs
Environmental Standards
ENERGY STAR Yes

Related Products

Below are the optional products related to the selected product.